Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
|
Gold Index: 9232
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Heat recovery unit modular ground source heat pump cooling heating hot water
Specifications
Basic modules | EKWD021CRDR/DV | EKWD032CRDR/DV | EKWD043CRDR/DV | |||
Underground circulation mode | Nominal Cooling Capacity | kW | 76 | 113 | 153 | |
Nominal Heating Capacity | kW | 79 | 115 | 159 | ||
Total Power of Nominal Cooling Capacity | kW | 13 | 20.4 | 27.2 | ||
Total Power of Nominal Heating Capacity | kW | 16.8 | 26.0 | 34.3 | ||
Water flow | Application side | m³/h | 13.1 | 19.4 | 26.3 | |
Heat source side | m³/h | 15.3 | 22.9 | 31.0 | ||
Heat Recovery Mode |
Nominal Cooling Capacity | kW | 67.7 | 102 | 137 | |
Nominal Heat Recovery Capacity | kW | 85 | 128 | 172 | ||
Total Nominal Power | kW | 17.3 | 26 | 35.0 | ||
Nominal water flow at the heat recovery side | m³/h | 14.6 | 22.0 | 29.6 | ||
Nominal water flow at the evaporation side | m³/h | 13.1 | 19.4 | 26.3 | ||
Water heater mode | Nominal Heating Capacity | kW | 72 | 109 | 146 | |
Total Nominal Power | kW | 20 | 30.6 | 41.0 | ||
Nominal water flow at the hot water side | m³/h | 14.6 | 22.0 | 29.6 | ||
Water flow at the heat source side (evaporation side) |
m³/h | 15.3 | 22.9 | 31.0 | ||
Water pressure drop |
Application side (air conditioner side) | kPa | 19 | 35 | 32 | |
Heat source side | kPa | 26 | 20 | 19 | ||
Heat exchanger type |
Application side (evaporator) | Plate | Shell-and-tube | |||
Heat source side (condenser) | Shell-and-tube | |||||
Recommended total pipe diameter |
Evaporator | mm | DN65 | DN65 | DN80 |