Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
|
Gold Index: 9232
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Ducted Chilled Water Horizontal Fan Coil Unit High ESP 100Pa
SPECIFICATIONS
MODEL |
200 DA |
300 DA |
400 DA |
500 DA |
600 DA |
800 DA |
900 DA |
1000 DA |
1200 DA |
1400 DA |
1600 DA |
||
NOMINAL AIR FLOW | H | cfm | 205 | 262 | 391 | 489 | 543 | 805 | 920 | 990 | 1397 | 1404 | 1861 |
M | cfm | 179 | 235 | 359 | 467 | 511 | 762 | 891 | 959 | 1299 | 1401 | 1749 | |
L | cfm | 118 | 159 | 262 | 371 | 408 | 641 | 761 | 809 | 981 | 1136 | 1360 | |
COOLING CAPACITY | TOTAL | W | 1660 | 2300 | 3280 | 3750 | 4300 | 6570 | 7150 | 7910 | 9980 | 10490 | 12920 |
SENSIBLE | W | 980 | 1400 | 2040 | 2580 | 2850 | 4490 | 4870 | 5480 | 7360 | 7880 | 9960 | |
HEATING CAPACITY | H | 3564 | 4541 | 6158 | 7351 | 8705 | 12709 | 14413 | 15498 | 20736 | 20887 | 25529 | |
RATED POWER INPUT | H | W | 84 | 101 | 116 | 148 | 165 | 297 | 299 | 309 | 507 | 603 | 665 |
M | W | 78 | 92 | 108 | 133 | 154 | 273 | 277 | 290 | 475 | 523 | 607 | |
L | W | 58 | 69 | 92 | 110 | 133 | 225 | 232 | 250 | 407 | 428 | 529 | |
RATED CURRENT INPUT | H | A | 0.40 | 0.48 | 0.54 | 0.67 | 0.81 | 1.44 | 1.53 | 1.58 | 2.37 | 2.78 | 3.10 |
M | A | 0.36 | 0.42 | 0.49 | 0.62 | 0.71 | 1.25 | 1.28 | 1.34 | 2.17 | 2.46 | 2.78 | |
L | A | 0.28 | 0.32 | 0.43 | 0.54 | 0.61 | 1.02 | 1.06 | 1.14 | 1.85 | 2.04 | 2.42 | |
WATER FLOW RATE | m3/h | 0.16 | 0.22 | 0.31 | 0.36 | 0.41 | 0.63 | 0.68 | 0.75 | 0.95 | 1.00 | 1.23 | |
WATER PRESSURE DROP | KPa | 3 | 6 | 13 | 6 | 8 | 10 | 13 | 11 | 14 | 16 | 20 | |
EXTERNAL STATIC PRESSURE | Pa | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | |
SOUND PRESSURE LEVEL | dDA(A) | 42.6 | 45.6 | 45.3 | 46.7 | 49.2 | 48.7 | 48.2 | 50.3 | 50.9 | 50.9 | 52.9 | |
CONDENSATE DRAIN PIPE | Rc3/4 | ||||||||||||
UNIT DIMENSION | LENGTH | mm | 677 | 827 | 927 | 997 | 1097 | 1427 | 1537 | 1727 | 1427 | 1527 | 1827 |