Post Offer Free
Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd  

Gold Index: 9232

You are here: home  > Residential Air Conditioning Air Cooled Modular Chiller 8 ton Heat Pump Unit

Residential Air Conditioning Air Cooled Modular Chiller 8 ton Heat Pump Unit 

Place of Origin: Zhejiang, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: EKAC 100B

29.5kW Residential Air Conditioners Heat Pump Small Air-cooled Cold Water Integrated Unit
 
<span style="fo

29.5kW Residential Air Conditioners Heat Pump Small Air-cooled Cold Water Integrated Unit

 

Specifications:

 

Technical data sheet

 

Model EKAC 100B
Nominal cooling capacity kW                         29.5                                                             
×103kcal/h 25.37
Nominal heating capacity kW 30
×103kcal/h 25.8
Total power of nominal cooling capacity kW 9.9
Total power of nominal heating capacity kW 9.8
Power supply 380V/3N~/50Hz
Refrigerant Type                                            R22
Flow control Electronic expansion valve
Water side heat exchanger Evaporator type Vacuum braze-welded stainless steel plate heat exchanger
Water flow for
cooling
3
m /h
5.1
Water flow for
heating
3
m /h
5.2
Compressor Type Fully hermetic volute compressor
Lubricant Mineral oil (SUNISO 3GS)
Fan Type Horizontal centrifugal water pump
Qty. 1
Water pump Type Horizontal centrifugal water pump
External lift m 13
Size of inlet/outlet water pipe connector Rc1-1/4
Dimensions (L/W/H) mm 992x845x1840
Sound dB(A) 64
Power cable
specification
Section area of live line 2
mm
6
Qty. of live lines PCS 3
Section area of null line 2
mm
4
Qty. of null lines PCS 1
Section area of grounding line 2
mm
6
Qty. of grounding lines PCS 1
Unit weight Net weight kg 305
Operating weight kg 340
Water system Accessory kit Model EKAC-WS10A
Water tank L 38
Expansion water tank L 8
Size of pipe connectors Rc1-1/4

 

Note:
Working conditions for nominal cooling capacity test: water flow rate 0.172m3/(h.kw); temperature of outlet water 7°C;
outdoor ambient temperature 35°C.
Working conditions for nominal heating capacity test: water flow rate 0.172m3/(h.kw); temperature of outlet water 45°C;
temperature of outdoor dry/wet bulb 7°C/6°C.
The sound level is tested before the unit leaves factory. Practically, due to environment noise and other factors, the sound level tested might
be different from those listed in the above table.
Please refer to the User Manual for specific operation ranges.

 

Description

 

1. Units of this series feature a classic European air conditioner design (chilled water/heat pump + indoor terminals) for precise temperature control. The units can provide you with a comfortable, healthy and graceful working/living environment. The uni ts feature a heat sink mechanism using circulatory air and needs no cooling tower. This not only saves the cost of the cooling tower, but also saves precious building space. Units of this series feature various models and dimensions to meet different installation requirements.

2. Units of this series are equipped with fully hermetic compressors which are stable, advanced and reliable. All components have undergone strict integration and compatibility test to ensure optimized performance and efficient/energy-saving operation all year round.  The EKAC100BR  integrated units perfectly unify the parallel compressor technology and electronic throttle technology to quickly modulate the cooling capacity to the set value, thereby making sure that the units are most energy efficient. The EER is even higher with partial workload. For example, for EKAC100BR unit, the EER is 6% higher with 75% of workload, 11% higher with 50% of workload, and 16% higher with 25% of workload. The solenoid interlock control function can shut down the master unit and water pump automatically when all fans have stopped working, making the unit more energy saving.

3. The EKAC100BR integrated unit features a 500-step PMV electronic expansion valve for precise PID flow control, dynamic and real-time adjustment of the cooling capacity and accurate water temperature control. An electronic expansion valve with a large flow modulation range helps optimize the performance of various parts of the system, and makes the system work reliably under any workload. The units can automatically adapt to changing ambient temperatures, completely eliminating cooling system vibration during the capacity modulation process.

4. Long and strict tests prove the unit can work reliably in an environment as hot as 48°C (cooling) or as cold as -10°C (h

bigPhoto
 Mr. Mr. Rocky

Tel: 86-769-83660888
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd [China (Mainland)]


Business Type:Manufacturer
City: Dongguan
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (193)