Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
|
Gold Index: 9232
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Modular Water Source/ Geothermal Heat Pump Unit
Specifications
Technical data sheet
SQ standard model for chilled water circulation
Basic modules | EKWD021CSQ | EKWD032CSQ | EKWD043CSQ | |||
Cooling mode | Nominal Cooling Capacity | kW | 74 | 110 | 150 | |
Total Power of Nominal Cooling Capacity | kW | 14 | 22.3 | 30.1 | ||
Water flow | Evaporator | m³/h | 12.7 | 18.9 | 25.8 | |
Condenser | m³/h | 15.1 | 22.8 | 30.9 | ||
Water pressure drop | Evaporator | kPa | 21 | 30 | 30 | |
Condenser | kPa | 17 | 19 | 19 | ||
Heat exchanger type | Evaporator type | Plate | Shell-and-tube | |||
Condenser type | Shell-and-tube | |||||
Recommended total pipe diameter |
Evaporator | mm | DN65 | DN65 | DN80 | |
Condenser | mm | DN65 | DN65 | DN80 | ||
Volume Adjustment | Steps | 2 | 3 | 4 | ||
Regulation mode | Fuzzy control | |||||
Compressor | Model | Fully hermetic volute | ||||
Lubricant | Mineral oil (SUNISO 3GS) | |||||
Refrigerant | Flow control method | Electronic expansion valve | ||||
Category | R22 | |||||
Dimensions | L x H x W | mm | 1647x1202x632 | 2247x1498x710 | ||
Unit weight | Net weight | kg | 452 | 703 | 887 | |
Transportation weight | kg | 478 | 738 | 922 |
Notes: Test conditions for the unit are as follows:
Test conditions for nominal cooling capacity: inlet chilled water temperature at the application side 12°C; outlet chilled water temperature at
the application side 7°C; inlet cooling water temperature at the heat source side 30°C; outlet chilled water temperature at the heat source
side 35°C.
The water main of the assembled unit needs to be made and mounted on site, and the diameter needs to comply with the design
specification.
The attached Y-shaped filter must be mounted at the water inlet of the evaporator of each unit.
The cooling water and chilled water of the unit must be softened to avoid scaling in the heat exchanger.
The water pressure drop of the unit does not include resistance of any external water pipe or component.
Basic modules of the assembled unit are EKWD032CRSQM/SM/S and EKWD043CRSQM/SM/S. A unit may be formed by modules of the
same model or different models.
Product specifications are subject to change due to upgrade without further notice.
Decription
1, The modular water source/geothermal unit supports applications in all conditions and can switch between multiple modes to fully meet user needs for cooling, heating, and hot water. With an innovative water system, the energy-saving unit delivers an EER as high as 5.7, provides higher energy efficiency when working at a partial workload, and saves energy by 50% compared with other systems after operation in a year.
2, The unit is designed with a comprehensive water system and consists of efficient components carefully selected and designed for a low operation noise. The unit supports fuzzy volume regulation for a narrow range of temperature changes and quickly reaches the set temperature. In addition, the unit provides hot water at a set temperature as high as 55°C quickly and steadily to meet requirements for comfortable hot water in all places..
3 With modular design, the unit starts step by step, reducing the shock on the grid, and maintenance of a single unit does not affect running of other units. In addition, the unit provides multiple built-in security protection functions, and supports intelligent and centralized control, facilitating daily management.
4, The leading-edge shell design allows the unit to be installed in an outdoor space such as terrace and rooftop without the need of a dedicated room. The unit delivers a long lifecycle and runs for long. Units may be installed in batches according to project progress. One water system that works in multiple modes saves investment on other devices such as heating and hot water supply devices, thereby saving the energy..
5, The 32RT and 43RT basic modules support free combination of master units and slave units to form 1 to 16 units, providing as many as 153 solutions for a cooling capacity as high as 688RT.
6, The unit sends control signals to valves of the water system to easily switch between the water source/geothermal heat pump mode, heat recovery mode, and water heater mode, meeting requirements for cooling, heating, and hot water around the clock.
7, The unit easily implements variable primary flow pumping, which helps the central air conditioning system save energy by 30%.
8, The modular design allows transportation by using elevators and manual forklifts and eliminates the need for hoisting.
9, The modular design allows units to be moved separately and assembled, facilitating installation work.
10, The
Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd [China (Mainland)]
Business Type:Manufacturer
City: Dongguan
Province/State: Guangdong
Country/Region: China (Mainland)