Model No.: EKRV-W

 
EKRV-W Series Friendly Refrigerant Multi-connected Underground Circuit Source Heat Pump Units
 

 

EKRV-W Series Friendly Refrigerant Multi-connected Underground Circuit Source Heat Pump Units

 

Parameter

 

Model

EKRV

080AR1W

EKRV

100AR1W

EKRV

120AR1W

EKRV

140AR1W

EKRV

160AR1W

Underground circuit Rated cooling capacity kW 23.2 28.8 34.0 39.1 46.4
Rated heating capacity kW 22.4 28.8 33.6 38.4 44.8
Rated cooling power kW 4.1 5.4 6.3 7.1 8.2
Rated heating power kW 5.0 7.0 7.7 8.5 10.0
Rated cooling current A 7.9 10.4 12.1 13.5 15.8
Rated heating current A 9.5 13.3 14.7 16.1 19.0
EER EER 5.7 5.3 5.4 5.5 5.7
COP 4.5 4.1 4.4 4.5 4.5
Rated water flow m3/h 4.7 5.9 6.9 7.9 9.4
Water pressure drop kPa 55 55 55 55 55
Power supply

380V/3N~

/50Hz

380V/3N~

/50Hz

380V/3N~

/50Hz

380V/3N~

/50Hz

380V/3N~

/50Hz

Sound dB(A) 46 50 52 52 50
W × D × H mm 650×550×700
Weight kg 120 160 165 170 240
Water pipe connector size Cooling water inlet pipe Rc1-1/4 Rc1-1/4 Rc1-1/4 Rc1-1/4 Rc1-1/4
Cooling water outlet pipe Rc1-1/4 Rc1-1/4 Rc1-1/4 Rc1-1/4 Rc1-1/4
Condensate water pipe connector φ19 steel tube φ19 steel tube φ19 steel tube φ19 steel tube φ19 steel tube
Pressure bearing capacity at water side MPa 2.0 2.0 2.0 2.0 2.0
Refrigerant R410A R410A R410A R410A R410A
Pipelining Gas side Welded Welded Welded Welded Welded
Liquid side Bell-mouthed terminal connected to threaded connector
Size of refrigerant pipe connector Liquid pipe Φ mm(in) 9.52(3/8) 12.7(1/2)
Gas pipe Φ mm(in) 22.23(7/8) 28.6(1-1/8)

 

 

Model EKRV180
AR1W
EKRV200
AR1W
EKRV220
AR1W
EKRV240
AR1W
EKRV260       AR1W EKRV280AR1W 
Underground circuit Rated cooling capacity kW 52.0 57.6 62.8 68.0 73.1 78.2
Rated heating capacity kW 51.2 57.6 62.4 67.2 72 76.8
Rated cooling power kW 9.5 10.8 11.7 12.6 13.4 14.2
Rated heating power kW 12.0 14.0 14.7 15.4 16.2 17.0
Rated cooling current A 18.3 20.8 22.5 24.2 25.6 27.0
Rated heating current A 22.8
bigPhoto
 Mr. Mr. Rocky

Tel: 86-769-83660888
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd [China (Mainland)]


Business Type:Manufacturer
City: Dongguan
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (193)